SOLAR MAX INVERTER,S SPECIFICATIONS
model | 1.2K | 2.4K | |
Input | |||
voltage | 230 VAC | ||
Voltage range | 170-280 VAC(narrow mode) 90-280vac(wide mode) | ||
OUTPUT | |||
Voltage regulation (BATT.MODE) | +/-10% | ||
Transfer time | 20 ms typical | ||
Wave form | Simulated since wave | ||
BATTERY | |||
Battery voltage | 12vdc | 24vdc | |
Floating charge voltage | 13.5vdc+_0.5 VDC | 27.0vdc+_0.5vdc | |
Maximum charge current | 10a or 20a | ||
CHARGE CELL | |||
Charging current | 50a | ||
System voltage | 12 VDC | 24vdc | |
Operating voltage range | 15~18 VDC | 30~32vdc | |
Max. PV array open circuit voltage | 40 VDC | 60vdc | |
PHYSICAL | |||
Dimension(DXWXH) mm | 300x252x104 | ||
Net weight (KGS) | 4 | ||
Use the table below to solve minor problems.
If there is any abnormal situation occur which dose not list above please search in menu side bar
PROBLEM | LCD/LED/BUZZER | EXPLANATION/POSSIBLE CAUSE | WHAT TO DO |
When power falls, the backup time is shorten , | Battery low alarm issue quickly , | Battery voltage is too low | Charge the unit at least 8 hours , |
Battery capacity is not full even after charge the unit for at least 8 hours , | Check the date code of the battery , if the batteries are too old , replace the batteries , | ||
Mains exist but the unit work in battery mode. | Input voltage is display as 0 on the LCD and LED is flashing | Input protector I tripped | Check if AC breaker is tripped and AC wiring is connected well , |
Green LED is flashing , | Insufficient quality of AC power (shore or generator ) | 1, check if AC wires are too thin and /or too long , 2, check if generator (if applied) is working well or if input voltage range setting is correct , (narrow-> wide) | |
Green LED is flashing , | Set solar first as the priority of output source, | Change output source priority to utility first, | |
No led display on the front panel when the utility power is normal , | No LED display, | Battery is not connected well, | Check the external battery cable and terminal, make sure all the battery connections to the unit are all correct, |
Battery defect , | Replace the batteries, | ||
Buzzer beeps continuously and red led is on , | Fault code 00 | Output short circuited, | Check if wiring connected well and remove abnormal load, |
Fault code 01 | Overload error, the inverter is overload 110% and time is up, | Reduce the connected load by switching off some equipment , | |
Fault code 03 | Output voltage too high | Return to repair center | |
Fault code 05 | Fan fault | Replace the fan | |
Fault code 06 | Internal temperature of inverter component is over 100 % temperature, | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high , | |
Fault code 08 | Battery is over charged, | Return to repair center, | |
The battery voltage is too high, | Check if spec and meet requirements, |
Great – I should certainly pronounce, impressed with your web site. I had no trouble navigating through all the tabs as well as related info ended up being truly easy to do to access. I recently found what I hoped for before you know it in the least. Reasonably unusual. Is likely to appreciate it for those who add forums or anything, site theme . a tones way for your client to communicate. Excellent task..