Win- va /vc,s deceleration / acceleration time has 4 options , to switch between these time option , please set deceleration / acceleration time option 1 ,2 at multi function input .
setting value 7 = acceleration / deceleration time selection 1 .
setting value 1 a = acceleration / deceleration time selection 2 .
according to the deceleration / acceleration time option 1 , 2 ,s on/of , the selected deceleration / acceleration time is as follows the deceleration/ acceleration time can be switched during operation .
acceleration time selection 1=acceleration/deceleration time 2 = acceleration time =deceleration time.
off or not set = off or not set = acceleration time 1 c 1-01 = deceleration time 1 c 1- =02.
on = off or not set = acceleration time 2 c 1-03= deceleration time 2 c 1- =04 .
off or not set = on = acceleration time 3 c 1-05 =deceleration time 3 =c 1-06 .
on =on =acceleration time 4 c 1-07 =deceleration time 4 =c 1-08 .
Emergency stop ( setting value , 15 ,17 )
When emergency stop is selected , multi function input is on , the inverter will deceleration to stop according to the deceleration time set by c1-09 ( emergency stop time ) to release the emergency stop please set the operation command and emergency stop both to be off.
When emergency stop is at contact b , please set it as 17 .
setting value 15 : emergency stop ( a contact deceleration to stop according to c1-09 when it is in on status ).
setting value 17 : emergency stop (b contact decelerate to stop according to c1-09 when it is in off status).
f jog command /r jog command (setting value 12,13
for/rev jog frequency operation is allowed
setting value 12 = f jog command on forward operation when pressing jog frequency (d1-09_
setting value 13= R jog command on forward operation when pressing jog frequency (d1-09)
F jog command and f jog command is prior to the other frequency command . when f jog command and r jog command are in the status of on for above 500 ms the inverter will stop according to the setting of b1-03 (stop method selection ) it is acceptable that either f jog command or f jog command is set it will be in a single operation status when for/rev command are not input frequency command terminal 13/14 selection (setting value ,1f ) when this function is set at multi function input terminal 13 or 14 operation can be switched.
off: the main speed frequency command is the analog signal from terminal 13 .
on : the main speed frequency command is the analog signal from terminal 14 .